Pennant PT25-15

Pennant PT25 Series Inverted Bucket Steam Traps

Pennant PT25-25

Pennant PT25-25

Pennant PT25-20, PT25-25L

MAINTENANCE:

This product can be maintained inline without disturbing

the piping connections. Ensure that the trap is isolated -

upstream & downstream - before attempting to dismantle

it. It is recommended that the trap be opened periodically

and the internals inspected for wear, damage, and dirt. All

worn or damaged parts should be replaced with new

spares. A full new internal kit comprising of the valve pin,

valve seat, bracket and lever, should be replaced as a set.

The bucket vent hole should be cleaned. The strainer

screen should be removed and cleaned regularly.

Ensure that the trap is primed by opening the inlet valve

only a crack at start-up, allowing water to fill the trap

before the steam enters.

The trap should be installed as close as possible to the

equipment to be drained.

For new pipelines, ensure that the lines are properly

flushed, prior to fitting the trap

IMPORTANT:

The inlet valve should be

opened fully only after the trap is filled with water.

DESCRIPTION:

FEATURES:

Inverted bucket steam trap with integral strainer and

all stainless steel internals. Best suited for

equipment drains with medium to heavy condensate

loads. Intermittent operation.

The inverted bucket arrangement operates on the

density difference between steam and water, giving

a cyclic operation for discharge of the accumulated

condensate.

High condensate handling capacities even at low

pressure, permit the use of small trap sizes to suit

many applications.

The valve and valve seat are hardened by a special

induction hardening process to withstand

continuous prolonged operation.

Perfect shut-off, no steam loss.

SIZES : ½", ¾", 1", 1½", 2"

CONNECTIONS: Screwed (NPT) / Socket weld /

Flanged (welded on)

INSTALLATION:

The trap should be fitted with the inlet and outlet

connections horizontally in-line. Correct fitment with body

vertical is essential for easymovement of the bucket. Care

must be taken to ensure that the trap level is below the

level of the equipment to be drained. The bypass

arrangement should be above the level of the trap.

Full port isolation valves should be fitted before and after

the trap, to be used when the trap has to be opened for

maintenance.

LIMITINGCONDITIONS:

Max. pressure rating 350 psig

Max. temperature rating 800ºF (½" to 1" size)

650ºF (1½" & 2" size)

Maximum operating back pressure at the outlet

should not exceed 90% of the inlet pressure.

Minimum diff. pressure for

satisfactory operation 1.5 psi

Request a Quote
Availability: In stock
SKU
PE01500W

MAINTENANCE:

This product can be maintained inline without disturbing

the piping connections. Ensure that the trap is isolated -

upstream & downstream - before attempting to dismantle

it. It is recommended that the trap be opened periodically

and the internals inspected for wear, damage, and dirt. All

worn or damaged parts should be replaced with new

spares. A full new internal kit comprising of the valve pin,

valve seat, bracket and lever, should be replaced as a set.

The bucket vent hole should be cleaned. The strainer

screen should be removed and cleaned regularly.

Ensure that the trap is primed by opening the inlet valve

only a crack at start-up, allowing water to fill the trap

before the steam enters.

The trap should be installed as close as possible to the

equipment to be drained.

For new pipelines, ensure that the lines are properly

flushed, prior to fitting the trap

IMPORTANT:

The inlet valve should be

opened fully only after the trap is filled with water.

DESCRIPTION:

FEATURES:

Inverted bucket steam trap with integral strainer and

all stainless steel internals. Best suited for

equipment drains with medium to heavy condensate

loads. Intermittent operation.

The inverted bucket arrangement operates on the

density difference between steam and water, giving

a cyclic operation for discharge of the accumulated

condensate.

High condensate handling capacities even at low

pressure, permit the use of small trap sizes to suit

many applications.

The valve and valve seat are hardened by a special

induction hardening process to withstand

continuous prolonged operation.

Perfect shut-off, no steam loss.

SIZES : ½", ¾", 1", 1½", 2"

CONNECTIONS: Screwed (NPT) / Socket weld /

Flanged (welded on)

INSTALLATION:

The trap should be fitted with the inlet and outlet

connections horizontally in-line. Correct fitment with body

vertical is essential for easymovement of the bucket. Care

must be taken to ensure that the trap level is below the

level of the equipment to be drained. The bypass

arrangement should be above the level of the trap.

Full port isolation valves should be fitted before and after

the trap, to be used when the trap has to be opened for

maintenance.

LIMITINGCONDITIONS:

Max. pressure rating 350 psig

Max. temperature rating 800ºF (½" to 1" size)

650ºF (1½" & 2" size)

Maximum operating back pressure at the outlet

should not exceed 90% of the inlet pressure.

Minimum diff. pressure for

satisfactory operation 1.5 psi