Control Air P200 Pneumatic-to-Current P/I Transducers
ControlAir’s Dahl P200 P/I transducer represents outstanding value in pneumatic to current technology. All solid state circuitry converts standard 3-15, 3-27 or 6-30 psig instrument air into 4-20 or 10-50 mA outputs (4-20 mA only for FM and CSA approval) with uncompromising accuracy and durability. Custom pressure ranges are also available. The P200’s explosion-proof housing allows it to stand up to the most hazardous and demanding applications. The P200 is FM approved and CSA certified as NEMA 4 (Enc. 4) for all locations and explosion-proof for Class I, Div. 1, Groups A, B, C, D; dust ignition-proof for Class II, Div. 1, Groups E, F, G; and suitable for Class III, Div. 1 locations.
ControlAir’s Dahl P200 P/I transducer represents outstanding value in pneumatic to current technology. All solid state circuitry converts standard 3-15, 3-27 or 6-30 psig instrument air into 4-20 or 10-50 mA outputs (4-20 mA only for FM and CSA approval) with uncompromising accuracy and durability. Custom pressure ranges are also available. The P200’s explosion-proof housing allows it to stand up to the most hazardous and demanding applications. The P200 is FM approved and CSA certified as NEMA 4 (Enc. 4) for all locations and explosion-proof for Class I, Div. 1, Groups A, B, C, D; dust ignition-proof for Class II, Div. 1, Groups E, F, G; and suitable for Class III, Div. 1 locations.
SPECIFICATIONS
Input |
3-15 psig (0.2-1 bar), 3-27 psig (0.2-1.8 bar), 6-30 psig (0.4-2 bar) |
---|---|
Input, Maximum |
3 times full scale without calibration 4 times full scale without failure |
Output (2 wire) |
4-20 mA, 10-50 mA |
Allowable loads |
700 Ω |
Accuracy |
± 0.15% of span guaranteed; ±0.10% of span typical. |
Hysteresis |
Negligible |
Repeatability |
±0.10% of span max; ±0.03% of span typical |
Resolution |
Infinite |
Output Ripple |
None |
Response Time to 99% of step change |
10 m Sec |
Temperature Stability |
Span and Zero: ±0.007% of span per ˚F maximum deviation from 77˚F calibration |
Power Supply Stability |
Less than 0.005% of span change in output per volt change at the input terminals |
Power Supply |
10 VDC min. to 42 VDC max. at input terminals. Can indefinitely withstand up to 100 VDC without failure |
RFI/EMI Effect |
Meets or exceeds SAMA PMC 33.1, 1978, 2-abc: 0.1% of span at 10 volts/meter |
Ambient Temperature Limits |
-40° to 161°F (-40° to 72°C) |
Temperature Range (Storage) |
-60° to 161°F (-51° to 72°C) |
Calibration Adjustments |
Multiturn span and zero potentiometers with approximately ±20% of span adjustment range |
Mounting Position Effect |
None |
In-process Output Monitoring |
Current: For accurate reading, ampmeter must have less than 20 Ω input resistance on 4-20 mA output (0.40 VDC drop) |
Connections - Signal Air |
1/4" NPT female |
Connections - Electrical Wiring |
1/2" NPT female to barrier terminal strip |