Control Air Type 600 Volume Booster
The Type-600 ratio relay volume booster is designed to use a pnuematic signal to produce an output pressure which has high flow capacity and can be amplified. This unit is most useful for systems requiring the conversion of a low flow control signal to the higher flow requirements of an operating system. Using an independent supply pressure for greater volume, the Type-600 relays up to 50 SCFM flow capacity to a final control element such as a valve actuator. The standard signal to output ratio is 1:1, however, the Type-600 is also available with an amplified ratio of 1:2, 1:3 and 1:6.
SPECIFICATIONS
Flow Capacity |
50 scfm (1415 Nl/min) |
---|---|
Port Size |
1/2" BSP, 1/2" NPT, 1/4" BSP, 1/4" NPT, 3/8" BSP, 3/8" NPT |
Signal Port Size |
1/4" NPT, 1/4" BSP |
Exhaust Port Size (optional) |
1/8" NPT |
Max. Flow Cv |
1 |
Exhaust Capacity |
15 to 10 scfm (425 to 283 Nl/min) |
Signal/Output Ratio |
1:1, 1:2, 1:3, 1:6 |
Sensitivity (depending on ratio) water column |
0.25" to 1.5" (0.64 to 3.8 cm) |
Ratio Accuracy- % of output span w/ 3-15 psig (0.2 to 1.05 bar) signal |
1.0% to 2.0% |
Zero Error- % of output span w/ 3-15 psig (0.2 to 1.05 bar) signal |
2.0% to 3.0% |
Supply Pressure Sensitivity |
0.1 to 0.6 psig for a change of 50 pis (3.5 bar) in supply pressure |
Air Consumption, Maximum depending on ouput range |
1.0 to 10 scfh (0.5 to 5.0 Nl/min) |
Max. Supply Pressure |
250 psig (17 bar) |
Max. Output Pressure |
150 psig (10 bar) |
Max. Signal Pressure depending on ratio |
150 to 25 psig (10.34 to 1.27 bar) |
Ambient Temperature Limits |
-40° to 160°F (-40° to 71°C) |
Weight |
1.4 lbs (635 gm) |
Mounting Options |
Pipe, panel, bracket |
Body Materials |
Aluminium |
Other Internal Materials |
Stainless steel, brass, plated steel, acetal, nitrile, polyester |