Control Air T900X Miniature I/P, E/P Transducer for Electronic Air Pressure Control
The Type-900X l/P, E/P transducers are a series of compact electronic pressure regulators that convert an electrical signal (current or voltage) to a proportional pneumatic output. Utilizing internal solid-state feedback circuitry, the Type-900X provides precise, stable pressure outputs to final control elements. Immunity to the effects of vibration or mounting position, high tolerance to impure air, and low air consumption make this unit ideal for use in demanding applications.
Request a Quote
Availability:
In stock
SKU
CA01700W
The Type 900X l/P, E/P transducers are a series of compact electronic pressure regulators that convert an electrical signal (current or voltage) to a proportional pneumatic output. Utilizing internal solid-state feedback circuitry, the Type 900X provides precise, stable pressure outputs to final control elements. Immunity to the effects of vibration or mounting position, high tolerance to impure air, and low air consumption make this unit ideal for use in demanding applications.
The heart of this unique technology is a bimorph piezo actuator that is encapsulated in a protective skin. This protective skin provides defense against the humidity and contaminants often found in process operating environments.
SPECIFICATIONS
Input |
0-10 Vdc, 0-5 Vdc, 1-5 Vdc, 1-9 Vdc, 4-20 mA |
---|---|
Output Range |
0-15 psig (0-1 bar), 0-30 psig (0-2 bar), 0-60 psig (0-4 bar), 1-17 psig (0.07-1.2 bar), 2-100 psig (0.14-6.9 bar), 2-60 psig (0.14-4 bar), 3-15 psig (0.2-1 bar), 3-27 psig (0.2-1.8 bar), 6-30 psig (0.40-2 bar) |
Air Consumption, Max. |
4.5 scfh (2.25 Nl/min) |
Air Consumption (Standard Range) |
1.5 scfh (0.75 Nl/min) |
Air Consumption (High Output Range) |
4.5 scfh (2.25 Nl/min) |
Flow Capacity, Maximum |
20 scfm (566 Nl/min) |
Flow Capacity at 25 psig supply - Standard Range |
4.5 scfm (0.75 Nl/min) |
Flow Capacity at 100 psig supply - Standard Range |
12 scfm (340 Nl/min) |
Flow Capacity at 130 psig supply - High Output Range |
20.0 scfm (566 Nl/min) |
Ambient Temperature Limits |
-40° to +158°F (-40° to +70°C) |