Control Air T595X Explosion-Proof I/P Transducer
The Type 595XP Explosionproof I/P (current to pressure) transducer converts a 4–20mA electrical current signal to a proportionally linear pneumatic output. The unique conversion technology utilizing open loop control provides a high level of accuracy and repeatability for the operation of actuated valves. A low mass control circuit provides consistent output in high vibration applications.
The Type 595XP Explosionproof I/P (current to pressure) transducer converts a 4–20mA electrical current signal to a proportionally linear pneumatic output. The unique conversion technology utilizing open loop control provides a high level of accuracy and repeatability for the operation of actuated valves. A low mass control circuit provides consistent output in high vibration applications.
This compact unit is housed in an explosion proof enclosure that is designed for pipe, bracket or direct manifold mounting. This explosion-proof and intrinsically safe field device is available with an integral volume booster or as a low-flow signal converter that directly mounts to a pneumatic valve positioner. The Type 595XP has worldwide agency approvals for use in hazardous areas.
Multiple choices for wiring and porting simplify installation and decrease the time required to do so. In addition to standard wall, panel or pipe mounting, optional DIN rail and manifold mounting kits are available. The ControlAir Type 925 Multifunction Manifold provides a common supply port and individual shutoff valves for sets of 3, 5, 10 or 15 units.
SPECIFICATIONS
Input |
4-20 mA |
---|---|
Output Range |
3-15 psig (0.20-1.0 bar), 3-27 psig (0.20-1.8 bar), 6-30 psig (0.40-2.0 bar) |
Max. Supply Pressure |
150 psig (10 bar) |
Air Consumption - P Connection (with Flow Booster) |
0.1 scfm (2.83 Nl/min) |
Air Consumption @ 85 psig (6.0 bar) - M & N Connection (without Flow Booster) |
4.94 scfh (2.47 Nl/min) |
Flow Capacity - P Connection (with Flow Booster) |
2.4 scfm (67.92 Nl/min) |
Flow Capacity @ 150 psig (4.18 Nl/min) - M & N Connection (without Flow Booster) |
8.36 scfh (4.18 Nl/min) |
Temperature Range (Operating) |
-40° to 158°F ('-40° to 70°C), -67° to 158°F (-55° to 70°C) |
Relative Humidity |
75% average – 95% short time non-condensing |
Impedance |
260 Ohms @ 70°F |
Linearity (Independent) |
<± 0.5% of span |
Repeatability - (±0.15% of span typical) |
<±0.3% of span |
Hysteresis |
<±0.3% of span |
Deadband |
<±0.1% of span |
Mounting Orientation Effect |
<±0.5% / 90 degree change |
Air Supply Sensitivity - P Connection (with Flow Booster) |
<0.3% / 1.5 psig (0.10 bar) change |
Air Supply Sensitivity - M & N Connection (without Flow Booster) |
<±0.6% / 25 psig (1.72 bar) change |
Vibration Effect |
<±1% up to 10g and 20-80 Hz |
Housing |
NEMA 4X (IP 65) |
Port Size |
1/4" NPT, 1/16 " Manifold Mount, 1/8" NPT Gauge Port |
Media |
Clean, dry, oil-free, instrument air, filtered to 40 micron |
Electrical Connection |
Terminal block |
Mounting |
Direct, 2" pipe |
Materials (Body) |
Aluminum, Plastic |
Materials (Other) |
Buna-N, Stainless Steel, Brass, Zinc-plated Steel |
Weight - P Connection (with Flow Booster) |
1.40 lbs. (0.64 kg.) |
Weight - M Connection (without Flow Booster) |
1.20 lbs. (0.54 kg.) |
Weight - N Connection (without Flow Booster) |
1.25 lbs. (0.57 kg.) |