Control Air T590X I/P Transducer
The Type 590X I/P (current to pressure) transducer converts a variable electrical signal to a linearly proportional pneumatic output. The small size, light weight and immunity to shock and vibration make it ideal for use in process control applications.
Conversion technology utilizing open loop control and a low mass magnet produces accurate pressure control at an economical cost. The Type 590X can mount in any position and is impervious to RFI/EMI interference.
Multiple choices for wiring and porting simplify installation and decrease the time required to do so. In addition to standard wall, panel or pipe mounting, optional DIN rail and manifold mounting kits are available.
The Type 590X I/P (current to pressure) transducer converts a variable electrical signal to a linearly proportional pneumatic output. The small size, light weight and immunity to shock and vibration make it ideal for use in process control applications.
Conversion technology utilizing open loop control and a low mass magnet produces accurate pressure control at an economical cost. The Type 590X can mount in any position and is impervious to RFI/EMI interference.
Multiple choices for wiring and porting simplify installation and decrease the time required to do so. In addition to standard wall, panel or pipe mounting, optional DIN rail and manifold mounting kits are available.
SPECIFICATIONS
Input |
4-20 mA |
---|---|
Output Range |
3-15 psig (0.20-1.0 bar), 3-27 psig (0.20-1.8 bar), 6-30 psig (0.40-2.0 bar) |
Air Consumption |
6 scfh (170 Nl/hr) |
Max. Supply Pressure |
42 psig (2.8 bar) |
Flow Capacity |
2.4 scfm (67.92 Nl/min) |
Ambient Temperature Limits |
-40° to +158°F (-40° to +70°C), -67° to +158°F (-55° to +70°C) |
Relative Humidity |
75% average – 95% short time non-condensing |
Impedance |
260 Ohms @ 70°F (21°C) |
Loop Load |
5.2 volts @ 70°F (26°C) |
Linearity (Independent) |
<+ 0.5% of span |
Hysteresis |
<+ 0.3% of span |
Deadband |
<+ 0.1% of span |
Repeatability |
<+ 0.3% of span; <+ 0.15% of span typical |
Mounting Orientation |
<+ 0.5% / 90 degree change (metric) |
Air Supply Sensitivity |
<+ 0.3% per 1.5 psig change |
Vibration Effect |
<+ 1% up to 10g and 20-80 Hz. |
Temperature Effect |
<+ 0.75% / 10°F change (metric) |
Housing |
Nema 1 (IP 20) |
Port Size |
1/8" NPT |
Media |
Clean, dry, oil-free, instrument air, filtered to 40 micron |
Electrical Connection |
Terminal block |
Mounting |
Pipe, DIN rail |
Materials (Body) |
Aluminum, Plastic |
Materials (Other) |
Buna-N, Stainless Steel, Brass, Zinc-plated Steel, Polypropylene |